Wire Size Calculator
NEC 310.16 ampacity, corrections and voltage drop, with every step shown.
How this wire size calculator works
It starts from the load. Continuous loads (3 hours or more) and motors are sized at 125% of their current; motor current comes from the NEC full-load current tables, not the nameplate. It then checks each conductor size from 14 AWG up:
- Terminations: the wire’s ampacity in the 60 °C or 75 °C column must cover the required current, because the lugs on breakers and equipment limit how hot the conductor may run.
- Corrections: the ampacity in the insulation’s own column is reduced for hot locations and for more than three current-carrying conductors in one raceway.
- Small conductors: 14, 12 and 10 AWG are limited to 15, 20 and 30 A breakers (copper) for general loads.
- Voltage drop: if you enter a length, the size is increased until the drop is within your target. 3% for a branch circuit is a common design goal.
Every step is listed with the result so an electrician or inspector can follow it. Have a question about your result? Ask our AI Engineer, or talk to one of our engineers about your panel or project.