Enclosure Heat Load Calculator

Fans, heat exchangers, air conditioners and heaters for control panels.

Enclosure size (inches, H × W × D)
Height
Width
Depth
Installation and material
Insulation
Heat inside the panel
Drives (total kW)
About 3% becomes heat (450 W)
Everything else
Power supplies, PLC, transformers

Total heat inside: 600 W (2,047 BTU/h)

Sun
Temperatures
Max inside the panel
95 °F (35 °C) is a common target
Hottest ambient
Valley summers: plan for 105-115 °F
Cold weather (optional)

Why control panels overheat

Every drive, power supply and transformer in a panel turns some of its power into heat. A VFD alone loses roughly 2 to 4% of what it delivers to the motor, so a panel with 15 kW of drives makes about 450 W of heat before you count anything else. The enclosure walls carry some of that out, depending on their surface area, material, insulation and how much hotter the inside is than the room.

When the walls can’t keep up, you need help. A filter fan is the simplest option, but only works when outside air is cooler than your target and the enclosure doesn’t need to stay sealed. A heat exchanger keeps a sealed enclosure sealed when the air outside is cool enough. In washdown areas, dusty plants or a Central Valley summer, a closed-loop air conditioner keeps the inside clean, dry and cool. Electronics last much longer below about 95 °F (35 °C).

Outdoors, the sun can add as much heat as a drive. A dark enclosure in full sun absorbs nearly twice the solar heat of a white or light gray one, and a simple sun shield with an air gap removes most of it. In winter, a small thermostat-controlled heater keeps condensation off the electronics.

Don’t want to add up datasheets? Use the parts list: paste in part numbers and quantities and AI looks up each part’s heat loss, with a link to its source. Or measure a running panel and let the calculator work out the heat for you.