4-20 mA Scaling Calculator

Milliamps, percent, engineering units and PLC counts. Type in any box.

Signal type
Instrument range
Low (LRV)
High (URV)
Units
Value (type in any box)
Signal
Percent of span
Engineering units
PLC raw counts (optional)
Raw count

How 4-20 mA scaling works

A 4-20 mA transmitter maps its calibrated range linearly onto the current loop: 4 mA is the lower range value (LRV), 20 mA is the upper range value (URV), and every milliamp in between is 1/16 of the span. A 0-150 PSI transmitter reads 75 PSI at 12 mA.

The “live zero” at 4 mA is why the signal is so popular: a reading near 0 mA means a broken wire or a dead transmitter, not a low process value. NAMUR NE 43 treats 3.8 to 20.5 mA as the normal measuring range and anything below 3.6 or above 21 mA as a failure signal, which is a good basis for PLC alarms.

PLC analog cards report a raw count rather than milliamps. Common full-scale values are 32767 (many Rockwell and generic cards), 27648 (Siemens), 4095 (12-bit) and 65535 (16-bit unsigned). Check your module’s manual for its exact range, then scale counts the same way.