4-20 mA Scaling Calculator
Milliamps, percent, engineering units and PLC counts. Type in any box.
How 4-20 mA scaling works
A 4-20 mA transmitter maps its calibrated range linearly onto the current loop: 4 mA is the lower range value (LRV), 20 mA is the upper range value (URV), and every milliamp in between is 1/16 of the span. A 0-150 PSI transmitter reads 75 PSI at 12 mA.
The “live zero” at 4 mA is why the signal is so popular: a reading near 0 mA means a broken wire or a dead transmitter, not a low process value. NAMUR NE 43 treats 3.8 to 20.5 mA as the normal measuring range and anything below 3.6 or above 21 mA as a failure signal, which is a good basis for PLC alarms.
PLC analog cards report a raw count rather than milliamps. Common full-scale values are 32767 (many Rockwell and generic cards), 27648 (Siemens), 4095 (12-bit) and 65535 (16-bit unsigned). Check your module’s manual for its exact range, then scale counts the same way.