Data Center Generator Fuel-Oil Controls
Industry: A Southern California data center (delivered as controls subcontractor to a mechanical contractor)
The challenge
The facility’s emergency generators needed a fuel-oil delivery system that would keep running through a controller or power-supply failure and report everything to the building management system (BMS).
What we did
- Designed, built and programmed a main tank control panel with two mirrored AutomationDirect DL06 PLCs that fail over automatically, dual UPS-fed power sources, redundant 24 VDC supplies, a C-more touchscreen, an E-stop, HOA switches and alarm history.
- Built five day-tank control panels, one per generator, each with its own PLC and touchscreen controlling the return pump and the supply and return valves, with a pump test function.
- Programmed alternating lead/lag supply pumps with automatic failover, day-tank fill and return logic, and leak and low-level interlocks from the tank monitoring and fuel filtration systems, with all PLCs sharing data with the BMS over Modbus/TCP.
- Built a separate dual-PLC make-up water control panel with tank level, pressure monitoring, pump speed control and Modbus data for the BMS.
- Delivered the O&M manual, drawings and submittals, and returned on site for service.
The result
The data center’s generator fuel and make-up water systems run on redundant controls that are fully visible in the BMS.
Platforms and equipment
AutomationDirect DirectLOGIC DL06, C-more, Modbus/TCP